How to download an application to a PanelView Plus via DH+?

To be able to download an application to the PanelView Plus via DH+, an application needs to be downloaded first via Serial or Ethernet to enable the DH+ connection, to do so please follow the following steps (If there is any existing DH+ configuration please delete the Drive from RSLinx Enterpsrise on the application (Design and Target) and reset to default RSLinx Enterprise configuration on the PanelView Plus):
  1. In FTView ME, go to RSLinx Enterprise and open Communication Setup.
    • In Design Tab, right click on RSLinx Enterprise --> Add Driver, then select DH+(1784-PKTX, 2711P-RN6,2711PRN8). On the DH+ properties interface, do not change anything, just press OK. Then Press the Button Copy from Derign to Runtime.
    • In the Runtime Tab, right click on the DH+ driver (DHPlus, DH+) then select Properties. Now change the Station Number (which should be "0") to "1" then press OK. 
  2. Press OK to close the Communication setup, then create a Runtime application and transfer it to the PanelView Plus using a serial or Ethernet connection. Make sur to enable Replace Communication on the Transfer Utility before downloading the application. 
  3. Once the PanelView Plus has rebooted, open again Transfer Utility and you should see your PanelView Plus Communication card showing up under the DH+ Driver, select it and download your application.   

2 comments:

  1. Post is very helpful for download an application to the PanelView Plus via DH+.

    via
    www.plc-scada-dcs.blogspot.com

    ReplyDelete
  2. hello
    What is the procedure, if use cable 1784-U2DHP?
    Thanks