To be able to download an application to the PanelView Plus via DH+, an application needs to be downloaded first via Serial or Ethernet to enable the DH+ connection, to do so please follow the following steps (If there is any existing DH+ configuration please delete the Drive from RSLinx Enterpsrise on the application (Design and Target) and reset to default RSLinx Enterprise configuration on the PanelView Plus):
- In FTView ME, go to RSLinx Enterprise and open Communication Setup.
- In Design Tab, right click on RSLinx Enterprise --> Add Driver, then select DH+(1784-PKTX, 2711P-RN6,2711PRN8). On the DH+ properties interface, do not change anything, just press OK. Then Press the Button Copy from Derign to Runtime.
- In the Runtime Tab, right click on the DH+ driver (DHPlus, DH+) then select Properties. Now change the Station Number (which should be "0") to "1" then press OK.
- Press OK to close the Communication setup, then create a Runtime application and transfer it to the PanelView Plus using a serial or Ethernet connection. Make sur to enable Replace Communication on the Transfer Utility before downloading the application.
- Once the PanelView Plus has rebooted, open again Transfer Utility and you should see your PanelView Plus Communication card showing up under the DH+ Driver, select it and download your application.
Post is very helpful for download an application to the PanelView Plus via DH+.
ReplyDeletevia
www.plc-scada-dcs.blogspot.com
hello
ReplyDeleteWhat is the procedure, if use cable 1784-U2DHP?
Thanks